JONLOO Pressure Reducing Valves are ready for dispatching

JONLOO Pressure Reducing Valves are ready for dispatching

YX741X Pressure Reducing Valve

The valve is composed of main valve, needle adjusting valve, ball valve and pipe system. This valve is mainly installed at the upstream of high-rise buildings,
living quarters and other pipe network, to reduce or maintain the pressure of downstream pipe network. Main valve adopts the structure of diaphragm type or piston type. 
Exit pressure is set by adjusting the pressure of relief pilot valve spring and needle valve open degree, and pressure is stabilized by feedback effect from pipe network and control room,
no other device or energy  needed, easy to maintain, less influenced by entrance pressure and flow, high accuracy of pressure controlling, reliable pressure reducing and maintaining.

 

Working Principle

When the pipe started water supply, water flows through needle valve into main valve control room, the outlet pressure  affect onto the pilot valve via tube. When the outlet pressure
is higher than pilot valve setting pressure,  pilot valve is closed, control room stops draining, main valve control room pressure rises and the main valve will be closed, the outlet
pressure will not rise any more.When the outlet pressure is lower than pilot valve setting pressure, control room drains to downstream. Pilot valve displacement is higher needle valve water inflow ,
main valve control room pressure reduces, main valve will be opened by inlet pressure. Under the stable state, control room inflow is the same as displacement, open degree will not change,
exit pressure will not change. Exit pressure could be set by pilot valve spring.
 
Features.
1 Pressure controlling is stable and reliable. Pilot valve and needle valve works continuously, pressure change of downstream is continuous and steady, less influenced by entrance pressure.
2 Easy to operate. After working pressure setting, when upstream pressure or flow changes, main valve will adjust automaticly to stabilize downstream pressure.
3 Valve adopts the design of full bore, straight-flow design, low head loss.
 
Parameters
Nominal
Pressure
Shell Test
Pressure
Seal Test
Pressure
Adjust Range
Suitable
Medium
Medium
Temperature
1.0 MPa
1.5 MPa
1.1 MPa
0.09-0.8MPa
 
 
Water
 
 
 
0-80℃
1.6 MPa
2.4 MPa
1.76 MPa
0.15-1.4MPa
2.5 MPa
3.75 MPa
2.75 MPa
0.2-2.0MPa
 